Skip to main content

Pumping station Aquapump F XL

Duo, SPF 3000-S1, D0

The pumping station for faecal and faecal-free wastewater is equipped with a submersible pump, a backflow preventer and a shut-off valve for the pressure pipe. The collection tank made of permanently resistant polymer (PE) has a closed pump tank (dry installation) with a screwed-on access cover. The station is controlled by a user-friendly control unit, which is optionally integrated in the building management system via a potential-free contact. Alternatively, alarm and collective fault messages can be output via a GSM interface. The KESSEL modular system provides different upper sections and engineering chamber options as accessories.

  • Maximum safety
  • Flexible installation
  • Hygienic advantages for maintenance and repair
Item no. 8742022
GTIN 4026092069585
Price group 60

Pumping station Aquapump F XL Duo, SPF 3000-S1, D0
The pumping station for faecal and faecal-free wastewater is equipped with a submersible pump, a backflow preventer and a shut-off valve for the pressure pipe. The collection tank made of permanently resistant polymer (PE) has a closed pump tank (dry installation) with a screwed-on access cover. The station is controlled by a user-friendly control unit, which is optionally integrated in the building management system via a potential-free contact. Alternatively, alarm and collective fault messages can be output via a GSM interface. The KESSEL modular system provides different upper sections and engineering chamber options as accessories. Type of wastewater: wastewater with sewage Installation situation: underground installation, floor slab installation Version: Type of system: Twin pump station Installation: Dry installation Shut-off valve: Shut-off valve made of polymer Pump control: Control unit Backflow preventer: integrated Access steps: yes Note on installation depth: Version with lowest installation height Delivery state: Pre-mounted for final assembly on site (pumps and sensor system must be fitted on site and control unit must be connected) General characteristics: Colour: black Standard: EN 12050-1 Dimensions: Length: 1,295 mm Width: 1,295 mm Height: 1,500 mm Tank: Number of inlets: 1 ST Inlet nominal size (DN): 150 Inlet nominal size (OD): 160 mm Distance pipe bottom inlet to tank bottom: 753 mm Distance from centre of outlet pipe to tank bottom: 1,343 mm Distance from centre of inlet pipe to tank bottom: 833 mm Tank volume: 335 l Pumping volume: 160 l Pressure pipe connection: horizontal Pressure pipe connection (DN): 80 mm Pressure pipe connection (OD): 90 mm Venting connection (DN): 70 mm Groundwater resistant from lower edge of base section: 3,000 mm Clear width of tank (LW): 1,000 mm Clear width of entry (LW): 800 mm Free passage: 40 mm Pumping device: Pump: SPF 3000 Number of pumps: 2 Max. pumping capacity: 47 m3/h Max. pumping height: 16 m Operating mode: S1 Power P1: 3.2 kW Power P2: 2.7 kW Speed: 2,890 U/min Max. temperature (permanent) of conveyed material: 40 °C Connection type: Direct connection Weight: 26 kg Impeller type: Multi-vane impeller Length of mains cable for pump: 10 m Rated current: 5.4 A Protection class (pump): IP 68 (3m/48h) Protection class: I Type of pump connection cable: H07RN-F 7G 1.5 mm2 Temperature monitoring: integrated Cos phi - power factor: 0.77 Insulation class: F Control: Control unit: Comfort Operating voltage: 400 V Mains frequency: 50 Hz Self-diagnosis system (SDS): yes Battery buffering: yes Multi-line display: yes Log book function: yes GSM interface: yes Potential-free contact: yes Type of fuse required (electrical protection): 3 x C 20 A Motor protection switch: yes Protection class control unit: IP 54 Length of mains cable for control unit: 0 m Type of level measurement: pneumatic Level measurement instrument: Immersion pipe Alarm sensor: Immersion pipe

Installation Video

  Title Item no.  
Upper section with cover plate LW 800, Class K 3, tileable 8740175 Show
Upper section with cover plate LW 800, Class K 3 with waterproof flange 8740176 Show
Upper section with cover plate LW 800, Class A/L15 8740177 Show
Upper section with cover plate LW 800, Cl. A/L15 with waterproof flange 8740178 Show
Upper section with cover plate LW 800, Class B 8740179 Show
Upper section with rectangular cover plate LW 800, Class D 8740180 Show
Upper section with cover plate LW 800, Class K 3 8740181 Show
  Title Item no.  
  Title Item no.  
Basic warning device with electronic probe 20222 Show
Basic warning device with optical probe 20223 Show
Compressor set for air bubbling 28048 Show
TeleControl GSM modem for Comfort control units 230V/400V 28792 Show
Connection box for level sensor extension 28799 Show
Intermediate section 250 mm, for chamber module LW 1000 680370 Show
Intermediate section 500 mm, for chamber module LW 1000 680371 Show
Replacement set optical probe 80888 Show
10 m probe cable extension set 80889 Show
Installation set Thermostat, Hygrostat 97713 Show
Outdoor control cabinet W: 590 mm, for control unit installation 97714 Show
Warning beacon for outdoor control cabinet 97715 Show
Outdoor control cabinet W: 460 mm, for control unit installation 97716 Show
Outdoor control cabinet W: 785 mm, for control unit installation 97723 Show
Outdoor control cabinet W: 1115 mm, for control unit installation 97724 Show
  Title Item no.  
Replacement set pump flange 28051 Show
Comfort control unit 400V, Aqualift Duo, 2x4.0-6.3 A 28758 Show
Battery 9 V block 680034 Show
Seal Pump flange 680045 Show
Screw set galvanised, 14 each 680047 Show
Pump flange SPF 1400 - SPF 4500 680050 Show
Seal for SPF 1400 - SPF 4500 680052 Show
Flap set Rolling ring, flap, flap holder 680053 Show
Immersion pipe for Aqualift F XL, 280 mm 680388 Show
Flap housing for Duo systems, with 2 shut-off valves 680419 Show
Cleaning cover screwed, DN 160 680421 Show
Seal set Pump flange 680422 Show
Pressure piping DN 90 680446 Show
Motor SPF 3000 / 400 V S1 10 m f. PS 680532 Show
  • Installation situation (ATTR-1): underground installation
  • TÜV test mark (ATTR-376): ID 1111241940
  • Country of origin (ATTR-322): DE
  • Area of application (ATTR-264): drainage
  • Pump type (ATTR-265): Freestanding pump
  • Pump shaft position (ATTR-266): vertical
  • Pump design (ATTR-267): Dry rotor pump
  • Pump hydraulics (ATTR-268): single stage
  • Pump suction characteristic (ATTR-269): non-self-priming
  • Pump drive (ATTR-270): E-motor for three-phase current
  • E-motor, type of startup (ATTR-271): direct
  • Pump casing material (ATTR-272): Grey iron
  • Upper tolerance of the operating voltage (+) (ATTR-273): 10  PROZ
  • Lower tolerance of the operating voltage (-) (ATTR-274): 10  PROZ
  • Upper tolerance of the nominal frequency (+) (ATTR-275): 3  PROZ
  • Lower tolerance of the nominal frequency (-) (ATTR-276): 2  PROZ
  • Pump electrical connection (ATTR-277): 3/N/PE 400V
  • Startup circuit for three-phase connection or three-phase current (ATTR-278): Star
  • Motor pump shaft (ATTR-279): continuous
  • Shaft seal (ATTR-280): MS
  • Number of operating pumps (ATTR-281): 1
  • Minimum pumped media temperature (ATTR-282): 0  CEL
  • Maximum operating pressure (Pmax) (ATTR-283): 1,600  HPA
  • Minimum speed for speed adjustment (ATTR-284): no speed adjustment
  • Start-up current (ATTR-285): 41  AMP
  • Vertical installation (ATTR-286): yes
  • Operating mode, twin systems (ATTR-287): redundant
  • Pump (ATTR-4): SPF 3000
  • Number of pumps (ATTR-181): 2
  • Impeller type (ATTR-8): Multi-vane impeller
  • Type of pump connection cable (ATTR-N2): H07RN-F 7G 1.5 mm2
  • Max. permissible switching frequency (ATTR-162): 20  1PH
  • Operating mode (ATTR-10): S1
  • Power P1 (ATTR-F4): 3.2  KWT
  • Power P2 (ATTR-F5): 2.7  KWT
  • Speed (ATTR-F2): 2,890  UMIN
  • Rated current (ATTR-N5): 5.4  AMP
  • Max. pumping capacity (ATTR-F7): 47  MQH
  • Max. pumping height (ATTR-F8): 16  MTR
  • Max. temperature (permanent) of conveyed material (ATTR-132): 40  CEL
  • Protection class (ATTR-133): I
  • Connection type (ATTR-N1): Direct connection
  • Protection class (pump) (ATTR-125): IP 68 (3m/48h)
  • Length of mains cable for pump (ATTR-11): 10  MTR
  • Temperature monitoring (ATTR-135): integrated
  • Weight (ATTR-191): 26  KGM
  • Cos phi - power factor (ATTR-192): 0.8
  • Insulation class (ATTR-193): F
  • Expected service life (hours of operation) (ATTR-194): 5,000  HUR
  • Expected service life (number of switching cycles) (ATTR-195): 150,000
  • Net weight (ATTR-A3A): 110.2  KGM
  • Gross weight (ATTR-A3B): 127.8  KGM
  • Shut-off valve (ATTR-A1): Shut-off valve made of polymer
  • Pressure pipe connection (ATTR-B7): horizontal
  • Type of system (ATTR-2): Twin pump station
  • Installation (ATTR-164): Dry installation
  • Backflow preventer (ATTR-165): integrated
  • Pump control (ATTR-134): Control unit
  • Access steps (ATTR-182): yes
  • Note on installation depth (ATTR-188): Version with lowest installation height
  • Length (ATTR-A6A): 1,295  MMT
  • Width (ATTR-A6B): 1,295  MMT
  • Height (ATTR-A6C): 1,500  MMT
  • Volume (ATTR-320): 3.7  MTQ
  • Packaging dimension: length (ATTR-325): 2,000  MMT
  • Packaging dimension: width (ATTR-326): 1,300  MMT
  • Packaging dimension: height (ATTR-327): 1,435  MMT
  • Dimensions (ATTR-323): 2000X1300X1435MM
  • Number of packages (ATTR-321): 1
  • Control unit (ATTR-S2): Comfort
  • Self-diagnosis system (SDS) (ATTR-S5): yes
  • Battery buffering (ATTR-S6): yes
  • Multi-line display (ATTR-S7): yes
  • Log book function (ATTR-S8): yes
  • GSM interface (ATTR-S10): yes
  • Potential-free contact (ATTR-S11): yes
  • Length of mains cable for control unit (ATTR-S12): 0  MTR
  • Operating voltage (ATTR-S13): 400  VLT
  • Mains frequency (ATTR-S14): 50  HTZ
  • Protection class control unit (ATTR-S4): IP 54
  • Alarm sensor (ATTR-S1): Immersion pipe
  • Type of level measurement (ATTR-7A): pneumatic
  • Level measurement instrument (ATTR-7B): Immersion pipe
  • Type of fuse required (electrical protection) (ATTR-S17): 3 x C 20 A
  • Motor protection switch (ATTR-172): yes
  • Clear width of entry (LW) (ATTR-B13): 800  MMT
  • Clear width of tank (LW) (ATTR-B14): 1,000  MMT
  • Number of inlets (ATTR-B1B): 1  PCE
  • Inlet nominal size (DN) (ATTR-B1CA): 150  MMT
  • Inlet nominal size (OD) (ATTR-B1CB): 160  MMT
  • Distance from centre of inlet pipe to tank bottom (ATTR-B6): 833  MMT
  • Distance pipe bottom inlet to tank bottom (ATTR-B1D): 753  MMT
  • Distance from centre of outlet pipe to tank bottom (ATTR-B15E): 1,343  MMT
  • Venting connection (DN) (ATTR-B4): 70  MMT
  • Pressure pipe connection (DN) (ATTR-B17): 80  MMT
  • Pressure pipe connection (OD) (ATTR-B18): 90  MMT
  • Tank volume (ATTR-B9): 335  LTR
  • Pumping volume (ATTR-B10): 160  LTR
  • Groundwater resistant from lower edge of base section (ATTR-B12): 3,000  MMT
  • Distance from inlet pipe invert to top of tank (ATTR-318): 747  MMT
  • Colour (ATTR-102): black
  • Standard (ATTR-9): EN 12050-1
  • CE marking (ATTR-A5B): yes
  • External monitoring (ATTR-A8): LGA
  • Free passage (ATTR-180): 40  MMT
  • Delivery state (ATTR-189): Pre-mounted for final assembly on site (pumps and sensor system must be fitted on site and control unit must be connected)
  • Declaration of Performance (DOP) (ATTR-292): 009-034
  • Wastewater quantity (ATTR-310): High
  • Type of wastewater (ATTR-6): wastewater with sewage
  • Declaration of conformity (ATTR-303): 009-034-D
  • Brand (M-ATTR-001): KESSEL
  • Product group (M-ATTR-002): Lifting stations
  • Product type (M-ATTR-003): Pumping station
  • Product family (M-ATTR-004): Aqualift
  • Product name (M-ATTR-005): Aqualift F XL