Skip to main content

Pumping station Aquapump XL

Duo, GTF1400-S1, 400V

The pumping station for faecal-free wastewater is equipped with a submersible pump and a backflow preventer. The collection tank made of permanently resistant polymer (PE) has an open pump tank with universal connection options. Quick-release closures enable the integrated components to be removed easily. The station is controlled by a user-friendly control unit, which is optionally integrated in the building management system via a potential-free contact. Alternatively, alarm and collective fault messages can be output via a GSM interface. The KESSEL modular system provides different engineering chamber options as accessories for the further layout. Stainless steel pump removal chains available as accessory for each installation depth - Article number: 680528 = Length 2 m 680529 = Length 3 m 680530 = Length 4 m 680531 = Length 5 m

  • Maximum safety
  • Flexible installation
  • Also handles large quantities of faecal-free wastewater
Item no. 8743048
Price group 60

Pumping station Aquapump XL Duo, GTF1400-S1, 400V
The pumping station for faecal-free wastewater is equipped with a submersible pump and a backflow preventer. The collection tank made of permanently resistant polymer (PE) has an open pump tank with universal connection options. Quick-release closures enable the integrated components to be removed easily. The station is controlled by a user-friendly control unit, which is optionally integrated in the building management system via a potential-free contact. Alternatively, alarm and collective fault messages can be output via a GSM interface. The KESSEL modular system provides different engineering chamber options as accessories for the further layout. Stainless steel pump removal chains available as accessory for each installation depth - Article number: 680528 = Length 2 m 680529 = Length 3 m 680530 = Length 4 m 680531 = Length 5 m Type of wastewater: wastewater with sewage Installation situation: floor slab installation, floor slab installation Version: Type of system: Twin pump station Installation: Wet installation Backflow preventer: integrated Passage seal for ventilation pipe (DN): 50 mm Passage seal for conduit pipe (DN): 63 mm Delivery state: Pre-mounted for final assembly on site (pumps and sensor system must be fitted on site and control unit must be connected) General characteristics: Colour: black Standard: EN 12050-2 Dimensions: Length: 1,300 mm Width: 1,300 mm Height: 1,416 mm Tank: Number of inlets: 1 ST Inlet nominal size (DN): 150 Inlet nominal size (OD): 160 mm Pumping volume: 350 l Pressure pipe connection: horizontal Pressure pipe connection (DN): 80 mm Pressure pipe connection (OD): 90 mm Pumping device: Pump: GTF 1400 Number of pumps: 2 Max. pumping capacity: 31 m3/h Max. pumping height: 10.5 m Operating voltage: 400 V Mains frequency: 50 Hz Operating mode: S1 Power P1: 1.5 kW Power P2: 1.1 kW Speed: 2,900 U/min Type of fuse required (electrical protection): C 16 A Max. temperature (permanent) of conveyed material: 40 °C Connection type: Direct connection Weight: 22 kg Impeller type: Multi-vane impeller Length of mains cable for pump: 10 m Rated current: 6.5 A Protection class (pump): IP 68 (20m) Protection class: I Type of pump connection cable: H07RN-F 3G 1.0 mm2 Temperature monitoring: integrated Insulation class: H Control: Control unit: Comfort Operating voltage: 400 V Mains frequency: 50 Hz Self-diagnosis system (SDS): yes Battery buffering: yes Multi-line display: yes Log book function: yes USB interface: yes GSM interface: yes Potential-free contact: optional Type of fuse required (electrical protection): C 16 A Motor protection switch: yes Protection class control unit: IP 54 Length of mains cable for control unit: 1.4 m Type of level measurement: hydrostatic Level measurement instrument: Level sensor Alarm sensor: Level sensor

Installation Video

  Title Item no.  
  Title Item no.  
  Title Item no.  
Basic warning device with electronic probe 20222 Show
Basic warning device with optical probe 20223 Show
Compressor set for air bubbling 28048 Show
Cable fastener Set for engineering chamber 28076 Show
TeleControl GSM modem for Comfort control units 230V/400V 28792 Show
Aerial with magnetic base for TeleControl Modem, Cable 2.5 m 28793 Show
Extension cable for aerial with magnetic base, L: 2 m 28794 Show
Connection box for level sensor extension 28799 Show
Pressure hose Sold by the metre, 6x4 mm 100 680071 Show
Seal for intermediate section 680125 Show
Intermediate section 250 mm, for chamber module LW 1000 680370 Show
Intermediate section 500 mm, for chamber module LW 1000 680371 Show
Connecting bolt set Set of 10 680373 Show
Replacement chain pumping statio. Stainless steel, length 2 m 680528 Show
Replacement chain pumping statio. Stainless steel, length 3 m 680529 Show
Replacement chain for pumping stations Stainless steel, Length 4 m 680530 Show
Replacement chain, pumping stat. Stainless steel, length 5 m 680531 Show
Replacement set optical probe 80888 Show
Sealing set Cable conduit, DN 100 85410 Show
Installation set Thermostat, Hygrostat 97713 Show
Outdoor control cabinet W: 590 mm, for control unit installation 97714 Show
Warning beacon for outdoor control cabinet 97715 Show
Outdoor control cabinet W: 460 mm, for control unit installation 97716 Show
Outdoor control cabinet W: 785 mm, for control unit installation 97723 Show
Outdoor control cabinet W: 1115 mm, for control unit installation 97724 Show
  Title Item no.  
  • Area of application (ATTR-264): drainage
  • Pump type (ATTR-265): submersible pump
  • Pump shaft position (ATTR-266): vertical
  • Pump design (ATTR-267): Dry rotor pump
  • Pump hydraulics (ATTR-268): single stage
  • Pump suction characteristic (ATTR-269): non-self-priming
  • Pump drive (ATTR-270): E-motor for three-phase current
  • E-motor, type of startup (ATTR-271): direct
  • Pump casing material (ATTR-272): Grey iron
  • Upper tolerance of the operating voltage (+) (ATTR-273): 5  PROZ
  • Lower tolerance of the operating voltage (-) (ATTR-274): 5  PROZ
  • Pump electrical connection (ATTR-277): 3/N/PE 400V
  • Motor pump shaft (ATTR-279): continuous
  • Shaft seal (ATTR-280): MS
  • Number of operating pumps (ATTR-281): 1
  • Minimum pumped media temperature (ATTR-282): 0  CEL
  • Maximum operating pressure (Pmax) (ATTR-283): 1,050  HPA
  • Minimum speed for speed adjustment (ATTR-284): no speed adjustment
  • Pump (ATTR-4): GTF 1400
  • Number of pumps (ATTR-181): 2
  • Impeller type (ATTR-8): Multi-vane impeller
  • Max. permissible switching frequency (ATTR-162): 20  1PH
  • Operating mode (ATTR-10): S1
  • Power P1 (ATTR-F4): 1.5  KWT
  • Power P2 (ATTR-F5): 1.1  KWT
  • Speed (ATTR-F2): 2,900  UMIN
  • Operating voltage (ATTR-131): 400  VLT
  • Mains frequency (ATTR-N4): 50  HTZ
  • Rated current (ATTR-N5): 6.5  AMP
  • Max. pumping capacity (ATTR-F7): 31  MQH
  • Max. pumping height (ATTR-F8): 10.5  MTR
  • Max. temperature (permanent) of conveyed material (ATTR-132): 40  CEL
  • Protection class (ATTR-133): I
  • Protection class (pump) (ATTR-125): IP 68 (20m)
  • Length of mains cable for pump (ATTR-11): 10  MTR
  • Weight (ATTR-191): 22  KGM
  • Insulation class (ATTR-193): H
  • Expected service life (hours of operation) (ATTR-194): 5,000  HUR
  • Expected service life (number of switching cycles) (ATTR-195): 150,000
  • Inlet nominal size (DN) (ATTR-B1CA): 150
  • Length (ATTR-A6A): 1,300  MMT
  • Width (ATTR-A6B): 1,300  MMT
  • Height (ATTR-A6C): 1,416  MMT
  • Number of packages (ATTR-321): 0
  • Type of system (ATTR-2): Twin pump station
  • Installation (ATTR-164): Wet installation
  • Backflow preventer (ATTR-165): integrated
  • Number of inlets (ATTR-B1B): 1  PCE
  • Inlet nominal size (OD) (ATTR-B1CB): 160  MMT
  • Pressure pipe connection (DN) (ATTR-B17): 80  MMT
  • Pumping volume (ATTR-B10): 350  LTR
  • Control unit (ATTR-S2): Comfort
  • Self-diagnosis system (SDS) (ATTR-S5): yes
  • Battery buffering (ATTR-S6): yes
  • Multi-line display (ATTR-S7): yes
  • Log book function (ATTR-S8): yes
  • USB interface (ATTR-S9): yes
  • GSM interface (ATTR-S10): yes
  • Potential-free contact (ATTR-S11): optional
  • Length of mains cable for control unit (ATTR-S12): 1.4  MTR
  • Operating voltage (ATTR-S13): 400  VLT
  • Mains frequency (ATTR-S14): 50  HTZ
  • Protection class control unit (ATTR-S4): IP 54
  • Alarm sensor (ATTR-S1): Level sensor
  • Type of level measurement (ATTR-7A): hydrostatic
  • Level measurement instrument (ATTR-7B): Level sensor
  • Type of fuse required (electrical protection) (ATTR-S17): C 16 A
  • Motor protection switch (ATTR-172): yes
  • - (ATTR-S21):
  • - (ATTR-S22):
  • - (ATTR-S23):
  • Wastewater quantity (ATTR-310): High
  • Type of wastewater (ATTR-6): wastewater with sewage
  • Colour (ATTR-102): black
  • Standard (ATTR-9): EN 12050-2
  • CE marking (ATTR-A5B): yes
  • Delivery state (ATTR-189): Pre-mounted for final assembly on site (pumps and sensor system must be fitted on site and control unit must be connected)
  • External monitoring (ATTR-A8): LGA
  • Brand (M-ATTR-001): KESSEL
  • Product group (M-ATTR-002): Lifting stations
  • Product type (M-ATTR-003): Pumping station
  • Product family (M-ATTR-004): Aqualift
  • Product name (M-ATTR-005): Aqualift S XL
  • Start-up current (ATTR-285): 52.2  AMP
  • Installation situation (ATTR-1): floor slab installation
  • Type of pump connection cable (ATTR-N2): H07RN-F 3G 1.0 mm2
  • Type of fuse required (electrical protection) (ATTR-N3): C 16 A
  • Connection type (ATTR-N1): Direct connection
  • Temperature monitoring (ATTR-135): integrated
  • Pressure pipe connection (ATTR-B7): horizontal
  • Passage seal for ventilation pipe (DN) (ATTR-183): 50  MMT
  • Passage seal for conduit pipe (DN) (ATTR-184): 63  MMT
  • Pressure pipe connection (OD) (ATTR-B18): 90  MMT